Air To Water Heat Pump

Description

The AirToWaterHeatPump asset models a two-port heat producer that delivers heat to the water network by consuming electricity. In the thermal network, it behaves as a controllable producer on one hydraulic circuit, unlike the four-port HeatPump asset that couples two water circuits.

The asset is mapped from ESDL HeatPump objects with two ports. The coefficient of performance (COP) is mapped from ESDL and is used to convert delivered thermal power into electrical power consumption. During simulation, the controller provides temperature, heat-demand, and pressure or mass-flow control setpoints.

Parameters

Parameter

Description

Unit

ESDL Asset Property

coefficient_of_performance

Ratio of thermal heat supplied to electrical power input

COP

pressure_supply

Supply pressure setpoint used in pressure-controlled mode

Pa

controller-set

temperature_in

Inlet temperature

K

controller-set

temperature_out

Outlet temperature

K

controller-set

heat_demand_set_point

Thermal heat supply setpoint

W

controller-set

Controlled Parameters

The controller supplies producer-style setpoints for the two-port heat pump:

Signal

Description

Unit

\(T_{in}\)

Inlet temperature (connection point 0)

K

\(T_{out}\)

Outlet temperature (connection point 1)

K

\(Q_{set}\)

Requested heat supply to the network

W

set_pressure

If true, pressure is prescribed. If false, mass flow is prescribed to satisfy the heat setpoint.

Additional simulation outputs

In addition to the default per-port outputs for mass flow, pressure, temperature, and volume flow, the air-to-water heat pump provides:

Signal

Description

Unit

heat_supply_set_point

Heat supply setpoint requested by the controller

W

heat_supplied

Actual heat supplied to the water network

W

electricity_consumption

Electrical power consumption derived from supplied heat and COP

W

Physics and Assumptions

The asset sets temperatures and either pressure or mass flow as producer boundary conditions. The primary physical relation is the heat-demand-to-mass-flow conversion on the water side, followed by calculation of actual supplied heat from solved mass flow and internal-energy difference.

Mass flow

When operating in mass-flow-controlled mode, the required mass flow is computed from the requested heat supply and prescribed inlet and outlet temperatures:

\[\dot{m} = \frac{Q_{set}}{c_p (T_{out} - T_{in})}\]

where:

\(\dot{m}\)

Mass flow rate [kg/s]

\(Q_{set}\)

Heat supply setpoint [W]

\(c_p\)

Specific heat capacity at the mean fluid temperature [J/(kg K)]

\(T_{in}\)

Inlet temperature [K]

\(T_{out}\)

Outlet temperature [K]

Heat supplied

The actual supplied heat is evaluated from solved internal energy and mass flow:

\[Q_{supplied} = (U_1 - U_0) \dot{m}_1\]

where:

\(U_0\)

Internal energy at inlet [J/kg]

\(U_1\)

Internal energy at outlet [J/kg]

\(\dot{m}_1\)

Outlet mass flow rate [kg/s]

Electricity consumption

Electrical power consumption is computed from delivered heat and COP:

\[P_{el} = \frac{|Q_{supplied}|}{COP}\]

This relation provides a direct interpretation of the reported electricity usage for a given thermal output.

Assumptions

  • The asset is modeled as a steady-state producer boundary on the water network.

  • COP is constant during a timestep.

  • Internal compressor and refrigerant-cycle dynamics are not modeled.

  • Internal pressure losses and thermal losses inside the asset are neglected.

  • The response to controller setpoints is instantaneous within the timestep.

Limitations

  • No part-load COP curve or temperature-dependent COP model.

  • No startup, shutdown, minimum runtime, or defrost behavior.

  • No explicit maximum electrical power cap in this two-port implementation.

  • This page documents only the two-port AirToWaterHeatPump; the four-port HeatPump has different physics and controls.