Heat Exchanger

Description

The HeatExchanger asset models a four-port water-to-water heat exchanger that transfers heat from a primary circuit to a secondary circuit. In the thermal network, the primary side acts as the side that releases heat and the secondary side acts as the side that receives heat. The asset therefore couples two hydraulic circuits without mixing their water streams.

The asset is mapped from ESDL HeatExchange objects. The ESDL Efficiency property is used to represent how much of the requested primary-side heat transfer appears on the secondary side. During simulation, the controller provides temperature and heat-demand setpoints for both sides, plus a signal that selects the hydraulic boundary condition on the secondary side.

Parameters

Parameter

Description

Unit

ESDL Asset Property

heat_transfer_efficiency

Fraction of requested primary-side heat transfer that is delivered to the secondary side

Efficiency

temperature_in_primary

Primary-side inlet temperature

K

not mapped from ESDL; set by controller

temperature_out_primary

Primary-side outlet temperature

K

not mapped from ESDL; set by controller

temperature_in_secondary

Secondary-side inlet temperature

K

not mapped from ESDL; set by controller

temperature_out_secondary

Secondary-side outlet temperature

K

not mapped from ESDL; set by controller

Controlled Parameters

The controller provides setpoints for both hydraulic sides of the heat exchanger:

Signal

Description

Unit

primary_temperature_in

Primary-side inlet temperature

K

primary_temperature_out

Primary-side outlet temperature

K

primary_heat_demand

Requested heat extraction on the primary side

W

secondary_temperature_in

Secondary-side inlet temperature

K

secondary_temperature_out

Secondary-side outlet temperature

K

secondary_heat_demand

Requested heat delivery on the secondary side

W

set_pressure

Selects whether the secondary side is operated through a prescribed pressure or a prescribed mass flow

The primary and secondary setpoints should be physically consistent. In particular, the requested secondary heat transfer should not exceed what the configured heat-transfer efficiency allows.

Additional simulation outputs

In addition to the default per-port outputs for mass flow, pressure, temperature, and volume flow, the heat exchanger asset provides the following additional outputs:

Signal

Description

Unit

heat_power_primary

Heat power transferred from the primary side

W

heat_power_secondary

Heat power delivered on the secondary side

W

heat_loss

Difference between reported primary-side and secondary-side heat power

W

Physics and Assumptions

The heat exchanger transfers energy between two water circuits while keeping the circuits hydraulically separated. In simulation, the primary side represents the circuit that gives up heat. The secondary side represents the circuit that receives that heat. The model is steady-state within each timestep and uses prescribed inlet and outlet temperatures to translate requested heat transfer into mass flow and reported heat powers.

Heat transfer efficiency

The configured heat-transfer efficiency, \(\eta\), relates the requested heat transfer on both sides:

\[Q_{secondary,set} = - \eta Q_{primary,set}\]

where:

\(Q_{primary,set}\)

Requested heat transfer on the primary side [W]

\(Q_{secondary,set}\)

Requested heat transfer on the secondary side [W]

\(\eta\)

Heat-transfer efficiency [-]

The negative sign reflects that heat leaving one side appears on the other side with the opposite sign. For \(\eta = 1\), the asset behaves as an ideal exchanger with equal heat-transfer magnitudes on both sides. For \(\eta < 1\), less heat is delivered to the secondary side than is removed from the primary side.

Mass flow

For each side, the requested heat transfer is translated into a mass flow using the prescribed inlet and outlet temperatures:

\[\dot{m} = \frac{Q}{c_p (T_{out} - T_{in})}\]

where:

\(\dot{m}\)

Mass flow rate on the selected side [kg/s]

\(Q\)

Requested heat transfer on the selected side [W]

\(c_p\)

Specific heat capacity at the mean fluid temperature [J/(kg K)]

\(T_{in}\)

Inlet temperature on the selected side [K]

\(T_{out}\)

Outlet temperature on the selected side [K]

On the primary side, this relation defines the mass flow needed to extract the requested amount of heat. On the secondary side, the same relation defines the mass flow for heat delivery when the asset is operated in mass-flow-controlled mode.

Heat powers and losses

After solving the network, the reported heat powers are evaluated from solved mass flow and the internal-energy difference across each side:

\[Q_{primary} = \dot{m}_{primary} (u_{out,primary} - u_{in,primary})\]
\[Q_{secondary} = \dot{m}_{secondary} (u_{out,secondary} - u_{in,secondary})\]

The reported heat loss is then:

\[Q_{loss} = Q_{primary} - Q_{secondary}\]

where:

\(u_{in}\) and \(u_{out}\)

Inlet and outlet specific internal energy on the selected side [J/kg]

\(Q_{loss}\)

Reported difference between primary-side and secondary-side heat power [W]

These outputs help users check whether the exchanger is transferring nearly all primary-side heat to the secondary side or whether a significant difference remains.

Operating modes and sign convention

The asset can operate with either a prescribed pressure or a prescribed mass flow on the secondary side. In mass-flow-controlled operation, the secondary-side flow is chosen to match the requested heat transfer and temperature lift. In pressure-controlled operation, the network hydraulics determine the resulting secondary-side flow.

Heat transfer on the two sides uses opposite signs. A heat flow reported as leaving the primary side corresponds to heat entering the secondary side. When interpreting results, compare the magnitudes of heat_power_primary and heat_power_secondary together with heat_loss.

Assumptions

  • The asset is modeled as a steady-state heat transfer element within each timestep.

  • The primary and secondary water circuits are hydraulically separated and do not mix.

  • The heat-transfer efficiency is constant during a timestep.

  • Prescribed inlet and outlet temperatures are applied directly.

  • Internal thermal capacity of the exchanger metal and contained fluid is neglected.

  • Internal pressure losses inside the exchanger are neglected in the asset model.

Limitations

  • No explicit heat-exchanger geometry, heat-transfer area, or approach-temperature model.

  • No temperature-dependent efficiency, fouling, or performance degradation.

  • No transient warm-up, cooldown, or thermal storage effects.

  • No explicit leakage, bypass flow, or cross-contamination between circuits.

  • If exchanger pressure drop is important for the study, a more detailed asset model is needed.